Your Position:Home > Products&Solutions > DF6373 Three Phase Smart Meter On-site Calibrator

Products&Solutions

Testing & Calibration Equipment
DF6373 Three Phase Smart Meter On-site Calibrator

Manufactured in the testing and calibration of the 0.1 Class(and below) single phase meter and three phase meter, the DF6373 three phase smart meter on-site calibrator has the functions of meter accuracy test, electrical parameter test, transformation ratio test, harmonic test, correction of the wrong connection, data storage and reading, etc.

  • ●With the application of the digital reactive measurement technology, the test process of the equipment won’t be affected by the unbalance of the voltage¤t, the unsymmetry of phase angle and the frequency changing;

    ●The equipment can test active(reactive) power, voltage, current, frequency and phase , it also has the all parameter software modification function;

    ●High brightness, high definition, high resolution(No less than 640*480),large color LCD display;

    ●Wide working voltage range: AC 30~480V.The equipment can ensure the accuracy of the energy metering;

    ●The equipment can test the positive sequence, negative sequence, zero sequence and the imbalance of the voltage and current;

    ●Voltage auto-switch:0-480V, Current input(direct):5A;

    ●Equipped with the 0.2 Class 5A Clamp Meter, the equipment can test the switching none repeating error, contact error, angle error. etc.

    ●With the light and beautiful design of the appearance, the equipment is convenience for using in the field.

  •  

    Test voltage, current range

    Voltage limit:0-480V

    Accuracy:0.05%Un

    Current limit:0-24A

    Accuracy:0.05%In

    Clamp connected:1A、5A、10A、20A、50A、100A。

    Accuracy:0.2%

    PT secondary load

    Admittance(ms): 99.99

     

    Accuracy:

    Less than ±2%, reading ±0.02ms

    Operation Load(VA):500

    Accuracy:

    Less than ±2%, reading ±0.02VA

    CT secondary load

    Impedance(Ω):10.00

    Accuracy:

    Less than ±2%, reading ±0.01Ω

    Operation Load(VA):75

    Accuracy:

    Less than ±2%, reading ±0.2VA

    Phase frequency measurement

    Testing Phase:0-360

    Accuracy:±0.05°

    Testing Frequency:45-65Hz

    Accuracy:±0.01Hz

    Secondary side loop voltage drop

     

    Ratio difference: 0 ~ ±10%

    Accuracy:±0.02%

    Phase angle: 0 ~ ±600′

    Accuracy:±0.5′

    Frequency:47.5Hz~ 52.5Hz

    Accuracy:±0.1Hz。

    Voltage:57.7V(1±20%)

    100V(1±20%)。


Contact

Email: imeter@dongfang-china.com                  Tel: (86)0535-2916790    Fax: (86)0535-2916291
Website: Https://en.dongfang-wisdom.com         Skype : bingather